| Reactive modules
can only be used when coupled in parallel with matching
sizes of resistive type, WA Series load banks. Coupling
of RM Series units with Wa Series load banks, will
provide a true power factor loading facility, typically
in kVa at 0.8 power factor. When the system is connected
to an electronic type controller the operator has total
control of loading the system and can choose to load
in kilowatts only, or in kVa with lagging power factor.
Variable power factor loading can be achieved from
0.3 to unity. Reactive modules are fan cooled, and
are fitted with auxiliary power sockets for independent
power supply, for the control switch gear. Units incorporate
an input socket and a 12 ft. long loop cable, for connection
to a matching resistive type load bank. |
|
 |
|
 |
|